Work item:
|
K.125 (ex K.idc)
|
Subject/title:
|
Dangerous effects and protective measures against electromagnetic disturbances when internet data centre is co-sited with high-voltage substation
|
Status:
|
Approved on 2017-07-29 [Issued from previous study period]
|
Approval process:
|
AAP
|
Type of work item:
|
Recommendation
|
Version:
|
New
|
Equivalent number:
|
-
|
Timing:
|
-
|
Liaison:
|
IEC
|
Supporting members:
|
-
|
Summary:
|
This Recommendation specifies the calculating methods for dangerous effects, tolerable limits of dangerous effects, tolerable limits of electromagnetic effects from high-voltage substation, distance requirement and protection methods, protective measures, as well as requirements of power frequency magnetic field immunity of server when an IDC is co-sited with a high-voltage substation.
The co-sites of IDC and high-voltage substation discussed in this Recommendation include proximity, co-earthing network, and co-building room.
This Recommendation is applicable to IDCs and large communication centres co-sited with high-voltage substations. For small internet data site, this Recommendation may not be applicable.
|